power.jpg (5308 bytes)

Welcome to Abbott Electronics.


 

General Power Supply
Application Notes

The following guidelines, arranged topically in alphabetical order, will help system designers and application engineers avoid many of the problem situations that could otherwise interfere with the successful application of Martek Power Abbott power supply modules.
clear_dot.gif (807 bytes)
Topics include:
AC Input Line Requirements
Martek Power Abbott's AC-DCpower supply modules contain two or three AC input circuit terminals designated as:
  • AC Hot (pin 1 if not designated)
  • AC Neutral (pin 2 if not designated)
  • Case or chassis (safety) ground
Figure 1 shows the correct way to wire these terminals. Take care to connect the AC Hot and Neutral lines (if designated) as shown. Interchanging them can result in circulating ground current. Connect the safety ground line to both the power supply chassis or case ground connector (if present) and to your system chassis. If the power supply chassis or case ground connector is not present, connect the safety ground directly to your system case or chassis. When connecting several power supplies to the same AC source, connect all AC Hot terminals together and connect all AC Neutral terminals together.
[Figure 1.] AC Input Line Circuit Requirements
Switches - As a minimum safety precaution, insert a single-pole switch or fuse in series with the AC Hot line or, for additional safety, a double-pole switch in series with the AC Hot and Neutral lines as shown in Figure 1.
Fuses -
For maximum protection and safety, always insert a fuse in series with the AC Hot line of the power supply module. Use Buss MDX type or equivalent slow-blow fuses rated as listed in the operating instructions accompanying each unit. Alternatively, use a delayed magnetic circuit breaker, such as the Heinemann Model CF (characteristic 1).

[Back to the Top]

Bypass and Decoupling Circuits
To minimize the effects of the power supply's output resistance (Rs) and the resistance (Ro) of the power distribution leads on fast analog or digital circuits, use one or more local decoupling capacitors (C1 and C2) in parallel with the load as shown in Figure 2. Decoupling circuits reduces the effects of resonance created by stray capacitance (Cs) and the supply and line inductance (Ls and Lo), and dampen any voltage spikes that are generated by load current transients. The two-capacitor decoupling circuit shown in Figure 2 bypasses both medium-frequency (C2) and high-frequency (C1) signals and reduces cross-talk between multiple loads.

[Figure 2.] Load Decoupling

Tobypass individual analog or digital circuits, always connect each bypass capacitor to prevent the AC signal from returning through the power supply module as shown in Figure 3. Keep signal current paths and lead lengths as short as possible.

[Figure 3.] Bypassing By Shortest Signal Path

[Back to the Top]

Conductor Size and Resistance
As shownin Figure 4, the resistance (Ro) of the load conductors and the contact resistance (Rc) at the power supply and load connection points can seriously degrade regulation and significantly reduce the load voltage. By neglecting these losses, a system designer could expect the output of a 5-V power supply rated at 0.1% regulation to vary by 5mV from no load to full load. However, if the losses represented, say 1.2%, of the available output, the same supply would degrade to 1.3% regulation at the load, and the load voltage would vary by 65 mV from no load to full load- an increase of 1300% over the ideal situation.

[Figure 4.] Load Connection Resistance Factors

  • To avoidthis problem, always consider the effects of conductor and connector resistances on the application and observe the following guidelines:
  • Forhigh-current applications, keep conductor lengths as short as possible and ue larger wire sizes (Table 1) as necessary to minimize resistive losses. When choosing wire sizes, use 1,000 circular mils per ampere as a general guideline.
  • Ensurethat there is adequate conductivity for high-current conduction paths on printed circuit boards to minimize the voltage drop along the conductor run. Use the cross-sectional area and length of the conductor run to calculate its resistance.
  • Wrapand solder all connections wherever possible.
  • Carefully clean banana plugs, spade lugs, and other friction type connectors to remove oxidation and corrosion.
  • Avoid using edge-type circuit board connectors in parallel for carrying high load currents. Variations in contact resistance can cause severe current imbalances and damage contacts.
Table 1. Maximum Resistance of Annealed Copper Wire (100°C) Size AWG No. Area Circular Mils Resistance Ohms/1000 Feet Size AWG No. Area Circular Mils Resistance Ohms/1000 Feet
0 105,500 0.14 12 6,530 2.23
1 83,690 0.17 13 5,178 2.80
2 66,370 0.22 14 4,107 3.54
3 52,640 0.28 15 3,257 4.45
4 41,470 0.35 16 2,583 5.63
5 33,100 0.43 17 2,048 7.08
6 26,250 0.56 18 1,624 8.95
7 20,820 0.70 19 1,288 11.27
8 16,510 0.88 20 1,022 14.21
9 13,090 1.11 21 810 17.92
10 10,380 1.40 22 642 22.60
11 8,234 1.76

[Back to the Top]

Connection Arrangements
In many cases, as single power supply module may not provide the exact voltage, current, or reliability required for your application. For these a series or parallel combination of two or modules may satisfy your needs. Series aiding (voltage adding) or parallel arrangements can increase the load voltage, load current, or reliability specifications of single modules subject to the following limitations.
SERIES CONNECTED SUPPLIES
To achieve the output voltage specification required by your application, connect power supply modules in series as shown in Figure 5 and described in the following guidelines:
  • Use the fewest number of modules to achieve the required voltage specification.
  • Selectclear_dot.gif (807 bytes) power supply modules with similar ratings.
  • Do notclear_dot.gif (807 bytes) exceed the output-to-case breakdown ratings for the models in question.
  • Never connect modules in series-opposing (voltage subtracting) configurations, since they can not sink sufficient current to operate safely in this way.
  • Protect clear_dot.gif (807 bytes)each module from reverse voltage caused by a load short-circuit by connecting reverse-biased diodes across the output of each series-connected supply as shown in Figure 5. Choose diodes with peak inverse voltage (PIV) ratings equal to at least twice the load voltage and with forward current ratings greater than the maximum load current.

[Figure 5.] Load Connection Resistance Factors

Note that for modules connected in series, the total line and load regulation specification meets the percentage but not necessarily the absolute voltage specification of that for the individual modules. Furthermore, the total ripple specification is the sum of the ripple specifications for each module. Note also that because their internal switching circuits are not synchronized, switching regulators typically generate beat frequency components of about 1 kHz that can interfere with the operation of other circuits.

PARALLEL CONNECTED SUPPLIES
To achieve the output current required by your application, connect power supply modules in direct parallel or master/slave parallel configurations as described in the following guidelines:

  • Select power supply modules with similar voltage ratings.
  • Usethe fewest number of modules to achieve the required current specification.
  • Makethe output leads from each module of equal length and as short as possible.
  • Provideadequate sinking for each module to dissipate the heat resulting from full-load operation.
  • Forlow-current applications, connect the power supply modules in a direct parallel arrangement as shown in Figure 6a. Set the output voltage of each module individually by turning on one module at a time and adjusting its output voltage to within 1% of the required value. Balance less-than- full -load currents by placing a small amount of resistance (R1 and R2) in series with the load as shown. Typically, R1 and R2 should approximately equal the output impedance of the power supply, which you can approximate by dividing the load regulation voltage by full load current. Note that balancing is extremely difficult, even with two equal resistors, and can seriously degrade output regulation as described in the topic "Conductor Size and Resistance." For tighter regulation, use the direct parallel arrangement with remote error sensing as shown in Figure 6b. This arrangement generally provides better regulation but poorer load sharing than the direct parallel arrangement with local error sensing. However, by adding a small amount of resistance (Rs) in series with the sensing leads as shown, you can modify the circuit characteristics to provide about the same load sharing as the direct parallel arrangement with local error sensing while improving load regulation by a factor of 2. Refer to "Remote Error Sensing" for additional information.

[Figure 6.] Direct Parallel-Connected Power Supplies

Forhigh-current applications, connect the power supply modules in a master/slave parallel arrangement as shown in Figure 7. This circuit uses resistors R1 and R2 to ensure load sharing as in the direct parallel arrangement with local error sensing. However, it also has an external error amplifier, which monitors the negative output of the master supply and greatly improves regulation. As the master supply remotely senses and regulates the load, the amplifier feeds and error-compensating signal to the sensing input of the slave supply to bring the output voltage of that supply into line with the master.

[Figure 7.] Master/Slave Parallel-Connected Power Supplies

Forapplications requiring 100% power redundancy, ensure that each power supply module has sufficient capacity and heat sinking to supply 100% of the load alone and connect them in a modified direct parallel arrangement as shown in Figure 8. In this circuit, diodes replace the resistors of Figure 6 and enable one module to fail without affecting the operation of the other. Note that the power supply output voltage must be specified 0.5 to 1 volt higher than the load voltage to compensate for the additional diode drops. Choose diodes with PIV ratings greater than the load voltage and forward current ratings greater that full load current. These diodes may dissipate high power, so adequate heat sinking is essential.

[Figure 8.] Input Protection Circuits

[Back to the Top]

Line Noise and Transients
In manymilitary applications, input line noise and transients form motors, generator, ignition systems, high-current switching circuits, and similar systems pose potential problems for power supply and power converter modules. Although Pi filters in the input circuits of the power supply modules prevent noise generated by the supply from affecting the power source, they also prevent power line noise from entering. For applications where these filters are not sufficient, you may require separate isolation transformers in the input circuit of the supply.

Power line transients are usually more serious than noise, because they can damage a power supply module. If you expect transients in your application to exceed the maximum rated input voltage of the supply module, use either of the two commonly used transient protection methods shown in Figure 9.
clear_dot.gif (807 bytes)
The first circuit in Figure 9 shows a power supply input that is protected by a fuse and metal oxide varistor (MOV). The MOV protects the supply by absorbing and dissipating transient voltages. The fuse is required to protect the input line from the most common failure mode of MOVs- a short circuit. MOVs are typically available in breakdown voltages of 25 V and higher.
clear_dot.gif (807 bytes)
The second circuit in Figure 9 shows a power converter input that is protected by a transient suppressor. Transient suppressors are sold by most semiconductor manufacturers and will protect the supply from short-duration transients.

[Figure 9.] Input Protection Circuits

[Back to the Top]

Overload Protection
Martek Power Abbott powersupply and converter modules employ two types of output overload protection, depending on the type of module:
  • Foldback current limiting
  • Foldback current limiting

Foldback current limiting protects switching regulator models from damage when an overload occurs by reducing, or folding back, both the output voltage and current as the load resistance ranges from maximum to short circuit as shown in Figure 10a. Figure 10a applies to Models BN, C, CC, LV, LLV, MH, V, W, WW, WL, and WWL. These modules resume normal operation automatically after the removal of an overload. Models B, S, SN and U turn off when an overload occurs. After removal of the overload, Model B recovers automatically, but Models S, SN and U can not resume normal operation until their inputs have been recycled. Foldback current limiting protects all of these modules by reducing input power under an overload or short circuit. For the overload protection characteristics of other series, please consult an Abbott sales engineer.

[Figure 10.] Overload Protection

Overload Trip Points
MODEL TRIP POINT
B Typically 200 to 300% of rated current, depending on the saturation point of the output transformer.
BA, M, MH, M300 110 to 130% of rated current.
BN, C, CC, LV, LLV, V, W, WW, WL, WWL 135 to 175% of rated current.
S, SN 150 to 250% of rated current, depending on the output surge current.
BC, MB, WM 110 to 120% for single output or main output of rated current.  120 to 140% for auxiliary of triple output modules of rated current.
AB, AW, AM 110 to 130% of rated current.
Constant current limiting protects Models BA, M, and UO2 from damage when an overload occurs by holding the output current constant as shown in Figure 10b. These modules resume normal operation after the overload is removed. However, unlike the protection provided by foldback current limiting, constant current limiting does not reduce the internal power dissipation of the module. Although each module can withstand short circuits of unlimited duration, the heat from long-term overloads can deteriorate components within the supply and seriously degrade the operating life of the module.
clear_dot.gif (807 bytes)
Please consult a Martek Power Abbott sales engineer for further information.

[Back to the Top]

Power Distribution
Designing anefficient power routing system is much more difficult than simply selecting a power supply with the proper voltage and current rating. For truly effective power distribution, the system designer must:
  • Decide whether one central or several distributed supplies are appropriate. For additional information on this topic, refer to "Connection Arrangements."
  • Paycareful attention to error-sensing and system grounding techniques.
  • Determineif or how much power redundancy is required. For additional information on this topic, refer to "Connection Arrangements."

Parallel Distribution - The parallel distribution scheme depicted in Figure 11, although simple, is satisfactory only for low-current applications where the voltage drop in the load conductors is negligible. In this network the voltage at each load depends on the current drawn by the other loads, and the possibilities for ground loops, load interaction, and poor regulation are prevalent.

[Figure 11.] Simple Parallel Distribution

 
Single Point Distribution
- The single-point, or radial, distribution network shown in Figure 12 provides much better performance than simple parallel distribution, because it eliminates the opportunities for ground loops and interaction among loads. The success of this technique requires a single pair of terminal connection points, a pair of heavy (low resistance) wires connecting the power supply module to each terminal point, and separate leads connecting the terminal points to each individual load.

[Figure 12.] Single Point Distribution

 
Combination Distribution - A combination system, incorporating both parallel and single-point distribution offers some advantages in applications where there are both heavy and light loads. As shown in Figure 13, the heavy loads connect to the power supply output in a single-point arrangement, and the light loads in a parallel arrangement.

For best performance, always connect the heavy loads nearest the power supply output, and the light loads farthest away.

[Figure 13.] Combination Distribution

 
Power distribution for analog and digital circuits requires separating and grounding each type of circuit as shown in Figure 14. To ensure that unwanted signals from one do not interfere with the other, observe the following guidelines:
  • Use separate power supplies for analog and digital circuits.
  • Do notallow low-level analog signals to share conduction paths with digital or power returns. Notice that there is only one ground point and that the paths between the analog and digital supplies are shared.
    Analyzeeach ground path separately to make sure that it goes directly to the single point ground with no shared path.
  • Workclosely with the layout draftsman to assure the correct physical layout of signal and power paths on each circuit board.

[Figure 14.] Analog and Digital Circuit Distribution

[Back to the Top]

 
Remote Error Sensing
The remote error-sensing feature of Abbott power supply modules enables them to maintain the load regulation specification of a power supply right at the load by compensating for voltage drops across the load conductors. Remote error sensing is especially suitable for high-current applications, where the load conductor voltage drop could seriously degrade the regulation specification.
Figure 15 shows
a typical remote error-sensing application. Each output terminal has its own error-sensing connection points (designated +s and -s), which connect to the load through shielded or twisted pair leads (24 AWG size wire recommended). For optimal performance the error-sensing leads carry much less current than the load conductors, and the shielded or twisted pair wiring prevents noise from entering and interfering with the regulation circuits. In operation, the error-sensing circuit detects any deviations from the nominal load voltage and compensates by automatically adjusting the voltage available at the output terminals. If the remote error-sensing terminals are not used, the supply operates normally with local error-sensing when the sensing terminals are connected to the appropriate output terminal.

[Figure 15.] Remote Error Sensing

[Back to the Top]

 

[Products] [Request Info.] [Terms & Conditions]
[Warranty Information] [Engineering Department]
[EMI Reports] [Environmental Reports] [Product Search]

 

Please send site comments / suggestions to our Webmaster

Martek Power Abbott, Inc.
1111 Knox Street
Torrance, CA 90502, USA

Tel: (310) 202-8820 Fax: (310) 836-4926

© 2007 Martek Power Abbott, Inc. All Rights Reserved.

This page last updated on March 19, 2008 06:57 PM.